POLE QUANTITY | 2 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 250.0 AMPERES DC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 4 BUS BAR |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 DC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 30000.0 DC ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
UNTHREADED MOUNTING HOLE DIAMETER | 0.562 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 ROTARY |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 250.0 TO 500.0 DC ALL LOCATIONS |
NONDEFINITIVE SPEC/STD DATA | ACB TYPE |
REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | AS DIFFERENTIATED BY MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE,OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
SPEC/STD CONTROLLING DATA | |
MANUFACTURERS CODE | 81349 |
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCE | MILC17587 |
THE MANUFACTURERS DATA | |
MANUFACTURERS CODE | 79500 |
DESIGN CONTROL REFERENCE | DKN30 |